Barrier Coating / Ignition Barrier / Exterior Rated
Part Number F1E
If you are looking for the best fire rated spray on the market, you have come to the right place. FIRESHELL® (F1E) is the only waterproof, 1-part, non-combustible, fire retardant, intumescing coating complying with AC 377 ICC ES for interior and exterior use. Our fire barrier foam expands up to 2000% and provides oxygen starvation when in contact with fire. This barrier coating / ignition barrier comes in both insulating and fire extinguishing versions and is a non-toxic, drain safe, no fuming, water-based coating. Protect your buildings and the people in them with fire rated spray from ICP Group. Fires are extremely unpredictable, so it is wise to use fire barrier foam as a necessary precaution.
Applications:
- Exterior exposed Closed cell/open cell spray foam, Foam panels, roof foam
- Exterior exposed foam coated piping, boat insulation, ships, barrier foam
- Cabins, barns, foamed attics, lumber, sheathing, siding, roofs
- Wild land structures, fireproof weather resistant applications, flexible ducts/hoses/pipes
Approvals:
- Approved Ignition Barrier over Foam
- E119 – 1hour & 2 hour rated wall assembly
- 1/2 Hour Non-combustible rated coating
- E84 Class “A” verified / zero flame, zero smoke
- ASTM weather ability
- ASTM E96 approved Vapor Barrier
- AQMD super compliant
- Meets code for cold storage, water treatment facilities and Public Storage Structure’s foam walls.
- Meets ICC urban/wild land interface code requirements for non-combustibility over wood and lumber
Coating Coverage:
- Up to 130 ft²/gallon coverage
ASTM E119 Test Reports
ASTM E119 | PART # | PRODUCT | D.F.T. | DESCRIPTION | SUBSTRATE | RESULTS |
---|---|---|---|---|---|---|
ASTM E119 coated closed cell sprayfoam 15 minute wall assembly test | F1E | FIRESHELL® Ultra | 16 mils | Fire Resistance Testing According to Modified ASTM E119 Specifications. | 4" Thick Polyurethane Insulation Foam | 16 Minute Rating |
ASTM E119 coated open cell sprayfoam 15 minute wall assembly test | F1E | FIRESHELL® Ultra | 21 mils | Fire Resistance Testing According to Modified ASTM E119 Specifications. | 11.5" of 0.5lb density Open Cell Sprayfoam Insulation | 34 Minute Rating |
ASTM E84 Test Reports
ASTM E84 | PART # | PRODUCT | D.F.T. | DESCRIPTION | SUBSTRATE | RESULTS |
---|---|---|---|---|---|---|
Class 'A' | F1E | FIRESHELL® Ultra | 15 mils | Standard test for surface burning characteristics of building materials | Douglas Fir framing lumber | Class "A" 30 minute non-combustible |
E84 | F1E | FIRESHELL® Ultra | 15 mils | Standard test for surface burning characteristics of building materials | Cement Board | Flame:0, Smoke:0 |
Miscellaneous Test Reports
MISCELLANEOUS | PART # | PRODUCT | D.F.T. | DESCRIPTION | SUBSTRATE | RESULTS |
---|---|---|---|---|---|---|
Vapor Barrier Test | F1E | FIRESHELL® | See Report | To determine the moisture vapor transmission characteristics of a coating film | Porous Test Charts | WVT = 0.5 grains/ft2/hour WVP= 0.9perms |
FSIS Incidental Contact | F1E | FIRESHELL® | NA | USDA Food and Safety Inspection Service Acceptance for Meat and Poultry Plants, "Incidental Food Contact" | NA | Compliant with USDA Regulations |
Mold Resistance | F1E | FIRESHELL® Ultra | NA | ASTM D-3273-05 Resistance to growth of mold on the surface of interior coatings in an environmental chamber. ASTM D-3274-02 "Evaluating degree of surface disfigurement of paint film by fungal growth or soil and dirt accumulation | Gypsum Wallboard | No Mold Growth |
ICC AC377 approved Ignition Barriers Test Reports
ICC AC377 approved Ignition Barriers | PART # | PRODUCT | D.F.T. | DESCRIPTION | SUBSTRATE | RESULTS |
---|---|---|---|---|---|---|
NFPA 286 with Acc. Criteria AC377 appendix A on CLOSED CELL FOAM | F1E | FIRESHELL® Ultra | 10 mils | Flame spread and heat release using Full Scale Room Corner over Closed Cell Foam | 2# closed cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A on OPEN CELL FOAM | F1E | FIRESHELL® Ultra | 10 mils | Flame spread and heat release using Full Scale Room Corner over Open Cell Foam | 1/2" open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A on OPEN CELL FOAM CRAWL SPACES | F1E | FIRESHELL® Ultra | 10 mils | Flame spread and heat release using Full Scale Room Corner over open cell foam | 3/4# open cell foam (10" walls, 11 1/2" ceiling) with F1E compared to 1/4" plywood room | superior to plywood, room meets AC377 |
NFPA 286 with Acc. Criteria AC377 appendix A BASELINE test | NA | NA | NA | BASELINE test: Flame spread and heat release using Full Scale Room Corner over Open Cell Foam | Foam (7" walls, 11" ceiling) under 1/4" plywood room | Plywood room fails at 4:29 min |